Valley Select2 error codes
An independent guide from FixMyPivot, not from the manufacturer. Brand and panel names are here only so you can find your own equipment.
19 listed for this panel. Tap one for the full explanation. These only apply to this panel. On a different panel the same code, light or message can mean something else.
All 19 error codes
- E01BBRAM checksum failed at power upStops the machineCall a technician
- E02EEPROM checksum failed at power upStops the machine
- E03Unit resets: logged every time the module is power cycled
- E04Power dropped below the low voltage limitStops the machine
- E05System safety: possible tower misalignment, drive unit stuckStops the machine
- E06Pump safety, pressure too low after the pressure delayStops the machine
- E07Pressure sensor out of range high (above 4.5 volts): transducer has failed
- E08Pressure sensor out of range low (below 0.5 volts): transducer failed or not installed
- E09Pressure high with pump off: logged after the pump is off 5 minutes with more than 7 psi
- E10Pressure sensor mechanical switch could be stuck: pump off 5 minutes and the switch still on
- E11Resolver angle jumping around, lube the J pipe
- E12Resolver out of range high, possibly disconnected: loose or shorted resolver wires
- E13Keypad, possible key stuck: a key held 10 seconds, or a failed keypad
- E14Forward/reverse sense, possible shortStops the machineCall a technician
- E18GPS communication error, after 10 seconds
- E19GPS signal loss, after 10 seconds: the position reading flashes when this happens
- E20DGPS signal loss: check for a clear path above the antenna
- E23PLC communications error (GPS v2 only), after 3 failed replies in a row
- E25GPS coordinates out of range
Safety
Center pivots run on high voltage and heavy moving machinery. Shut off and lock out power at the main disconnect before you open a panel or touch anything electrical. If you are not sure, stop and call your local pivot dealer or a licensed electrician. These pages tell you what a code means. They do not replace a qualified technician, and the safety instructions that came with your equipment come first.
FixMyPivot is an independent troubleshooting service. It is not affiliated with, authorized by, or sponsored by any equipment manufacturer. All brand, panel and product names are trademarks of their owners and are used here only to identify the equipment a code appears on. This information is general, is provided as is without warranty, and may not match the software version on your panel. Use of these pages is subject to our Terms of Service.